Liquid coolers chill out


( 01 Jan 2008 )

by Jon Titus, Senior Technical Editor, ECN

Liquid cooling provides a convenient way to remove heat from electronic components, boards, and systems. Its efficiency exceeds that of moving air, and liquid-cooling equipment does not require air channels throughout an enclosure.



Some engineers may think of liquid cooling and picture leaking pipes and damaged electronics. Fortunately, liquid cooling has moved from the prove-it-to-me stage to routine use in high-end computers and military-and-aerospace equipment. So, just think of liquid cooling as a reliable and efficient way to move heat from one place to another. The removed heat can travel some distance to a radiator that dissipates the heat into outdoor air, municipal water, seawater or even another cooling system.



Liquid-cooling techniques fall into two categories; those that transfer heat to a liquid and those that use heat to vaporize a liquid. Figure 1 shows the cooling capabilities of four types of cooling. To investigate how vendors can help customers apply liquid cooling, ECN talked with people at four companies that produce liquid-cooling products.

Cooligy

From the start, Cooligy has focused on liquid cooling and developed a closed-loop cooling system that requires no service. “Engineers can buy components and assemble a liquid-cooling system,” said Fred Rebarber, director of sales and marketing at Cooligy, a division of Emerson Network Power. “But they must ensure everything works together, assure customers of long-term reliability and guarantee service-free equipment. That can be a heavy added burden,” Rebarber noted Cooligy has shipped 50,000 liquid-cooling systems for use in high-end PC workstations and so far, no system has required service.



Typically, Cooligy’s engineers work with a customer to model liquid cooling techniques and include them in a design from the start. Engineers may fear a liquid leak in their equipment, so Cooligy’s liquid-cooling products offer double redundancy. “We have designed our own connector barbs and tubing, and we use a proprietary sealant,” explained Rebarber. “Clamps and epoxy also ensure a no-leak cooling system, and the permeability of our flexible tubing approaches that of metal.”



Everyone has a different layout of the components they need to cool, and they have space and performance requirements. “Our micro hear-exchangers efficiently transfer heat from a chip to the liquid,” said Rebarber. “We can make heat exchangers to cool a spot or zone on a chip or to uniformly cool an entire chip package. Heat exchangers can form a series loop to extract heat from many parts in equipment.” Cooligy uses the same building blocks in many designs, so it does not have to design everything from scratch for new customers.



Engineers may wonder about the performance of cooling liquids at low temperatures. “PCs may have a temperature range between -40ºC and up to 85ºC,” explained Douglas Werner, Cooligy’s senior director of research and development. “But this temperature range is usually a shipping spec, not operating temperatures. We have standard fluids that perform like an antifreeze solution, but we also offer a glycol-free, water-based solution. Water has a high heat capacity, and it will not hurt the environment. If you add a glycol-based antifreeze, you decrease the liquid’s heat capacity and increase its viscosity. So, you get less efficient heat removal.”



Parker-Hannifin

Parker-Hannifin concentrates its liquid-cooling technologies on commercial off-the-shelf (COTS0 computer boards used in commercial, military and aerospace applications. The company’s electronics enclosures with liquid-cooled side walls provide heat removal for conduction-cooled board modules that use a thermally conductive frame. Heat flows from hot components through the frame to the edges of the circuit board. Liquid coolant circulates through the enclosure’s side walls that mechanically hold board modules in place and remove heat from individual boards. “For a typical 6 x 90inch board, liquid side-wall cooling lets us remove just under 200W, which approaches the practical limit for this cooling technique,” said Andy Odar, a systems engineer at Parker. “Liquid flow-through modules, on the other hand, raise the heat-removal capacity to 1,000W per board. Because these modules remove heat directly from its source and eliminate the heat-conducting frame, engineers prefer them in new applications that have high heat-load requirements.”



Figure 2 shows a liquid-cooled demonstration enclosure that accepts electronic boards and a pump module that circulates fluid through a cooling manifold. “The pump and boards plug directly into the backplane and manifold,” explained Odar. “The drip-less liquid couplings keep the electronics and the chassis dry.” If engineers prefer an external pump, the can use one. According to Odar, the internal pump can cool several enclosures, depending on the total heat load.



“One of our customers has an air-cooled electronics enclosure that measures approximately 8 x 5 x 3 feet. The enclosure contains a large number of sub-system drawers, each of which contains many boards that produce over 3,000W of waste heat,” said Odar. “The customer needed to move a lot of cool air through the equipment. We can remove the same amount of heat from a standard enclosure that measures roughly 8 x 10 x 20 inches.” Parker’s liquid-cooled demonstration enclosure complies with the Air Transport Rack (ATR) ARINC-404 standard and accepts board modules built to the emerging VME VITA 46/48 standards. The demo enclosure accepts as many as 11 modules and an optional pump module, and it can dissipate up to 4,000Q with coolants such as water or water/glycol solutions. Dielectric cooling fluids reduce the cooling capacity to approximately 2,000W.



Parker’s flow-through modules use macrolaminate structures that force fluid to flow over specific hot components or areas. “We can fabricate complex flow-channel patterns in thin sheets of aluminum or stainless steel,” explained Odar. “Then we bond these layers and machine the assembly to its final shape. Customers get a compact thin coldplate they can use in a chasses side wall, in a board module, or on a component.:



“Liquid cooling lets engineers think about their electronic designs from a different perspective,” said Rex Harvey, principal engineer at Parker. “Often, engineers continue to accept the limits of air cooling, which has approached its peak. Instead, they should think, ‘What can our electronics do now that liquid cooling removes most thermal limits?’ It does not make much sense to add liquid cooling to an existing design or to a new design that raises performance only slightly. But, when engineers include liquid cooling as an integral part of a system, they can achieve much better performance and reduce the size of their product.”



Amulaire

Some liquid-cooling equipment suppliers serve specialized markets. Amulaire Thermal Technology, for example, offers liquid-cooled cold plates and liquid-cooling systems that mate with drive electronics in hybrid and electric vehicles and in high-energy electrical devices such as quad-core CPUs, MRI machines and lasers.



“Engineers must realize that liquid cooling does not simple replace air cooling,” emphasized David Bono, director of sales and marketing at Amulaire. “Instead, it lets the engineers increase the performance of efficiency of a product. They can get more power from IGBT modules or overlock a CPU, for example.”



Unfortunately, many engineers do not want to “mix” water or other fluids with electronics. But, vehicle manufacturers have used liquid cooling for many years and computer manufacturers now offer liquid-cooling systems in off-the-shelf PCs. But to engineers familiar with only air-cooled products, liquid-cooling still can look a bit scary. Now, they must think about a pump, a radiator, fan, hoses and clamps, a cold plate and a fluid in addition to their electronics.



“Automotive engineers already have radiators and pumps in cars, so for them, liquid cooling does not present a big barrier,” said Bono. “Using the existing coolant ‘loop’ to cool power electronics in hybrid vehicles saves cost, weight and space. Because the loop delivers coolant to equipment at an ‘inlet’ temperature of 85ºC, you need an efficient cold plate. Say an electronic module has a maximum operating temperature of 12ºC. That gives you a delta-T of 35ºC to work with.”



According to Bono, a typical IGBT produces approximately a two-percent loss of energy as heat. “Our cooling technology gives engineers about a 20ºC delta-T for a 2,000W module, so even high-power modules can use a vehicle’s existing cooling loop.”



“To efficiently move heat away from hot spots, engineers want as much surface area as possible in a liquid-cooled cold plate, and, they want a high flow rate to dissipate that heat,” said Bono. Amulaire molds copper cold plates that include round ‘nanoprints’ that provide a large surface area that water can easily flow around. You can buy cold plates with smaller channels, but you need a lot of pressure to get liquid through them.



If a liquid-cooling system involved dissimilar metals, Bono cautions engineers to prepare for galvanic corrosion. “When you mix copper and aluminum in a loop, you can have problems. So, if engineers specify a copper cold plate, they must ask if any aluminum exists within the coolant loop.” The coolant can transport ions, and electronics can flow through electrical paths that may not appear obvious. Even without a direct electrical path, you can have problems. Corrosion inhibitors in the water capture ions, but you must replenish the inhibitors periodically.



“When we sell a copper to cold plate to a company that supplies its own pump, radiator and fluid, they know how to solve the corrosion problem, or they do not mix metals,” said Bono. “If necessary, we can nickel plate the copper cold plate to prevent galvanic corrosion.”



SprayCool

SprayCool offers two types of phase-change cooling systems; those that spray non-conductive coolant on a heat-exchange plate and those that spray the coolant directly on a board or assembly. Tahir Cader, technical director at SprayCool noted the company currently has a liquid-cooled product for the military that has operated for over 55,000 hours. And, SprayCool has delivered indirect cooling systems for IBM computers used at national lab.



“Sometimes, engineers show us an air-cooled device and say ‘We want to liquid cool this,” said Cader. They have designed for air cooling, so we must add cooling components to the existing product, which can dramatically increase cost. When they design for liquid cooling from the start, they lower the cost, decrease product size, and increase performance.



In a direct-spray application, customers can use their existing cPCI, VME, and other cards that comply with 6U standards,” explained Andrew Finch, lead systems engineer and product marketing manager at SprayCool. “They do not change their electronics. They take a COTS boards, remove the heat sinks and put the boards directly into our Multi-Platform Enclosures that can accommodate from four to 20 6U cards.” The enclosures include atomizers that spray coolant between the cards. “We can direct the spray at hot chips, or we can spray an entire card rather than focus on specific components,” said Finch.



Sealed, or indirect-spray, modules attach directly to processors and absorb heat through a plate that separates the spray from the processor. “We can select modules, so if you have a quad-core package or a Pentium chip, they each get the right amount of cooling.” The sealed cooling modules take the place of heat sinks and use the same mounting hardware.



“In the military and aerospace industries, people have an aversion to maintaining liquid-cooled equipment,” noted Finch. “So, we provide a basic fluid-handling tool that lets technicians fill or drain cooling systems. Then they service the equipment just as they would air-cooled or conduction-cooled electronics.”



Click here for Illustrations:



Figure 1, Figure 2, Figure 3, Figure 4, Figure 5, Figure 6



 

 
 
 
ADVERTISEMENT
 
 
 
Ads by Google
 
OUR SPONSOR
   
   
 
 
 
   
   
     
 
 
         
     
 
Related Articles
   
Low-cost 5W termination
Configurator changes how engineers work
High-performance PC/104 CPU module
Enhanced SMC board-to-board adapter
Miniature circular connectors
Industry’s “largest” area laser beam profiling system
Wi-Fi cold storage monitor with years of battery life
Dual band WiFi front-end module
Compact ZigBee network module
SMT connectors offer secure mating retention
   
 
Business and Technology News
   
Industry Giants Unite to Deliver Mobile Broadband Future
embWiSe announces SDIOWorx support on Freescale's iMX31 and iMX27
Managing Data Center Complexity as Most Effective Way to Improve IT Efficiency
e-Shuttle and Hong Kong Science and Technology Parks Collaborate to Provide Silicon Shuttle Services for Asian Start-ups
Altera Partners with Farnell-Newark in Providing the Latest Field Programmable Technology in Asia
Global Semiconductor Industry Outlook Remains Positive
Instrumentation Evolution through Embedded Systems: Q&A with National Instruments' Chandran Nair
Asia’s Electronics Manufacturing Industry Shows Resilience amid Global Uncertainties
TippingPoint Wins Network Products Guide Reader Trust Award for Best in Network Access Control
Agilent Technologies' Asia Wireless Test Tour to Conclude in Hong Kong Tomorrow
   
  More News >>
 
     
     
 
         
 
 
     
         
 
spacer
Country Report
spacer
   
bullet

TAIWAN: Inductor technologies are developed independently

bullet

KOREA: Inductor manufacturers are highly competitive, but scarce

bullet

CHINA: World’s high-volume producer of transformer, coil and inductor

bullet

TAIWAN: Moderate but steady growth in LED market

bullet

KOREA: LED has a bright future in our homes

  more on country report >>
   
 
spacer
Our Sponsor
spacer
   
bullet
 
   
 
     
 
     
 
spacer
Features
spacer
   
bullet

Effective way of converting rotary motion to linear

bullet

Bluetooth connectivity enable remote patient monitoring

bullet

Power-management solutions for telecom systems improve performance, cost, and size

bullet

Exponentials simplify linear circuit analysis (part two)

bullet

Design tips cut FPGA power use

  more on features >>
   
 
Distribution
   

The five commandments of outsourcing

Dealing with distributors even when there are manufacturers around

Value addition is the key in distribution

Distributors supply solutions, not just parts

Taiwan distributors compete by bolstering in-house R&D

  more on distribution >>
   
 
     
         
 
 
     
         
 
Industry Focus
   

Ethernet adoption encourages open protocols

Managing Bluetooth profiles: A billion served

Enabling a true wireless multimedia home network

Bluetooth paves the way for truly wireless car interiors

Eliminating massive clock trees in SoC designs using GALS

  more on industry focus >>
   
 
Web Exclusives
   

Power-management solutions for telecom systems improve performance, cost, and size

Changing the network security playing field

WiMAX “personality pack” provides complete IEEE802.16 functionality

LED: A tiny light source with a bright future

SSDs: Carving a Niche in the Consumer and Enterprise Markets

  more on web exclusives >>
   
 
     
     
   
     
 
Semiconductors
   

Simulating the effect of blockers on data converter performance in wideband receivers

Decrease processor power consumption using a CPLD

Taking full advantage of new, low-power MCUs

Power train integration for 2007 and beyond: The true dawn of multi-chip modules

Wireless network options for industrial applications

  more on semiconductors >>
   
 
Field Applications
   

Test Equipment

Power Sources/Circuit Protection

Advanced Signal Processing Dramatically Improves Capability of Artificial Limbs

Voice Interface Technology for Hands-free Function in Automobiles

LXI: A Technology Leap for Test Instrumentation

  more on field applications >>
   
 
     
     
   
     
     
 
INDUSTRY LINKS
   
Photonics Association (Singapore)
bullet Singapore Industrial Automation Association (SIAA)
   
 
 

 

 
         
 

 
 
 
 
 
© 2008 Reed Business Information, a division of Reed Elsevier Inc.
All rights reserved. Use of this web site is subject to its Terms and Conditions of Use. View our Privacy Policy.